E30 Technical Specifications*
Electrical Input
Nominal Voltage 208, 220, 230 and 240 Vac
Input Voltage Ranges 160–288V (without using batteries)
Input Power Factor >0.95 typical
Frequency 50/60 Hz, auto-sensing
Frequency Range 46–65 Hz
Electrical Output
On Utility Voltage Regulation ±3% of nominal
On Battery Voltage Regulation ±3% of nominal
Efficiency 89–92% depending on load
Frequency Regulation ±3 Hz online; ±1 Hz on battery
Load Crest Factor 3 to 1 ratio
Communications
Communication Port RS-232 communication port standard; optional X-Slot cards available
Communication Cable 6-ft Serial (DB-9 to DB-9) and 6-ft (RJ-45 to DB-9) cables included
Battery
UPS Internal Battery Type 9 Ah, sealed, maintenance-free lead-acid
UPS Internal Battery Type 9 Ah, sealed, maintenance-free lead-acid
Battery Runtime See Battery Runtime Chart
Battery Replacement Hot-swappable UPS internal batteries and external batteries modules
Recharge Time <2 hours from complete discharge to 80% capacity at nominal line conditions
Start-On-Battery Allows start of UPS without utility input
General
Topology True online, double-conversion
Diagnostics Full system self-test on power up
UPS Bypass Automatic on overload or UPS failure
Dimensions and Weight See Model Guide
Environmental and Safety
Ambient Operating Temperature 0°C to 40°C (32°F to 104°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Relative Humidity 0% to 90% noncondensing
Heat Dissipation 186666 BTU/hr, maximum
Leakage Current <0.6 mA typical
Audible Noise <45 dBA typical
REPO Port Meets NEC code 645-11 intent and UL requirements
Network Transient Protector In and out jack for models only or 10BaseT network cable protection. UL497A tested
Safety Markings CSA, VDE, CE, S, D, N, FI, B, NOM, R
EMC Compliance FCC Class B and VCCI Class II, 3000 FCC Class A
Surge Suppression IEEE/ANSI C62.41 Category B (formerly 587)
* Due to continuing product improvement programs, specifications subject to change without notice.