Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications
24
E33 Technical Specifications*
Electrical Input
Nominal Voltage 208, 220, 230, and 240 Vac
Input Voltage Ranges 154–288V
Frequency 50/60 Hz, auto-sensing
Frequency Range 46–65 Hz
Electrical Output
On Utility Voltage Regulation -10% to +6% of nominal
On Battery Voltage Regulation ±5% RMS
Voltage Wave Shape (on battery Sine wave
Output Protection Short circuit protection
Battery
Battery Type Sealed, maintenance-free lead-acid
Battery Runtime See Battery Runtime Chart
Battery Replacement Hot-swappable UPS internal batteries and external batteries modules
Recharge Time <3 hours to 90% usable capacity
Start-On-Battery Allows start of UPS without utility input
General
Diagnostics Full system self-test on power up
UPS Bypass No bypass, internal bypass
Transfer Time 2-4 ms typical
Dimensions and Weight See Model Guide
Communications
User Interface Front control panel
Audible Alarms For UPS alarm conditions, including: On Battery, Low Battery, Overload, & UPS fault
Network Transient Protector UL497A, in/out jacks RJ-45
REPO Port Meets NEC code 645-11 intent and UL requirements
X-Slot Interface RS-232 Single-Port Serial Card (standard); other options available
Cable 6-ft communication (DB-9 to DB-9) cable included
Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)
Environmental and Safety
Operating Temperature 0 to 40°C (32 to 104°F)
Storage Temperature -15 to 50°C (5 to 122°F)
Relative Humidity 0% to 95% noncondensing
Heat Dissipation 695 BTU/hr, maximum
Lightning & Surge Protection ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5
Surge Energy Rating 480 Joules
Audible Noise <40 dBA typical
Altitude 3000m (10,000 ft) without derating
Safety Certifications UL; cUL; NOM; C-Tick; CE mark
EMC Compliance FCC Part 15, EN50091-2, Class A
* Due to continuing product improvement programs, specifications subject to change without notice.