Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications
36
Environmental and Safety
Operating Temperature 0 to 40°C (32 to 104°F)
Storage Temperature -20 to 50°C (-4 to 122°F)
Relative Humidity 0% to 95% noncondensing
Heat Dissipation 2066 BTU/hr (605.5W) maximum
Lightning & Surge Protection ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5
Surge Energy Rating High-energy 6500A peak
Audible Noise <55 dBA at 5 feet with battery fully charged, without horn
Altitude 3000m (10,000 ft) without derating
Leakage Current <3.5 mA
Surge Suppression ANSI C62.41 Category B3
Safety Certifications UL 1778; CSA C22.2, No. 107.3; EN and IEC 62040-2; NOM-019-SCFI-1993;
Agency Markings cULus, cUL, NOM, CE
EMC Compliance FCC Part 15, EN 50091-2, ICES-003
Seismic Uniform Building Code (UBC) and Bellcore for Zone 4 Earthquake
* Due to continuing product improvement programs, specifications subject to change without notice.