E83 Technical Specifications*
Electrical Input
Nominal Voltage 220 default, optional; 200, 208, 230, and 240 Vac
Input Voltage Ranges 220/230/240; 174-288V or 200/208; 160–253V,
Frequency 50/60 Hz, auto-sensing
Frequency Range 45-65Hz
Default Frequency 60Hz
Maximum Input Current at Nominal
Utility Voltage
48A
Noise Filtering MOVs and line filter for normal and common mode noise
Connections 9.9ft/3-meter IEC309 P+N+G 63A (363P6W) power cord
Input Power Factor >0.99
Input Mode
Single-phase with input power cord. Three-phase input available when input power
cord removed.
Electrical Output
Regulation Nominal output voltage +/- 2% Static, +/- 10% Dynamic
Nominal Outputs
200/208/220/230/240
(voltage configurable or auto-sensing)
45/48/45/43/41A
9/10/10/10/10 kVA
7.2/8/8/8/8 kW
Output Overload
100-110%: Activates Overload alarm
110-130%: load transfers to Bypass mode after 1 minute
130-150%: load transfers to Bypass mode after 1 second
>150%: load transfers to Bypass mode after 100 ms
Voltage Waveform
Normal mode: Sine wave; <3% THD with linear load;
<5% with nonlinear load
Output Receptacles
(4) IEC-320-C19, 16A
(1) IEC309 P+N+G 63A (363C6W)
Battery
Battery Type Sealed, maintenance-free, valve-regulated, lead-acid
Monitoring Advanced monitoring for earlier failure detection and warning
Configuration (32) 12V, 5 Ah
Battery Runtime See Battery Runtime Chart
Battery Replacement Hot-swappable UPS internal batteries and external batteries modules
Charging (in minutes) to 80% usable
capacity at nominal line voltage after
full load discharge
UPS Internal Batts +1 EBM +2 EBMs +3 EBMs +4 EBM
266 336 368 398 419
Start-On-Battery Allows start of UPS without utility input
General
Battery Module Replacement Yes, hot-swap
Diagnostics Full system self-test on power up
UPS Bypass Internal bypass
Dimensions and Weight See Model Guide
Communications
User Interface Front control panel, with two-line graphical LCD with backlight
Languages User selectable
Audible Alarms
For various UPS alarm conditions, including: On Battery, Low Battery, Overload, and
UPS Fault
REPO Port Meets NEC code 645-11 intent and UL requirements
Communication Ports Native USB and serial port (DB-9)
X-Slot Interface Empty; other X-Slot options available
Cable Two (2) 6-ft communication cables (DB-9 to DB-9 and RJ-45 to DB-9) included
Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)