EATON 9395 UPS (650–825 KVA) SINGLE-FEED KIT INSTALLATION
Eaton 9395 UPS (650–825 kVA) Single Feed Kit S 164201773 Rev 2 www.eaton.com/powerquality
2
5. Using tie wraps from the single-feed kit (see Table 1), secure cables to the
internal cabinet divider (see Figure 1).
6. Return to the applicable Eaton 9395 UPS manual to complete the wiring. Use
M12 50mm bolts from the single-feed kit (see Table 1) to install rectifier input
lugs.
Single Feed Jumpers
from Kit (4 per phase)
Rectifier Input
Terminals
Bypass Input
Terminals
Bus Bar
Extensions
1 M12 45mm Bolt, 2 Flat
Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)
1 M12
50mm Bolt from
Single-Feed Hardware Kit
(18 places)
2 Flat Washers, 1 Conical
Washer, and 1 Nut from
UPS Hardware Kit (18 places
)
1 M12 45mm Bolt, 2 Flat
Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)
1 M12
45mm Bolt, 2 Flat
Washers, 1 Conical Washer,
and 1 Nut from UPS
Hardware Kit (6 places)
NOTE Install bus bar extensions to back side of rectifier input bus bars to provide clearance for bolts and wires.
NOTE Verify each rectifier phase terminal is jumpered to the same phase on the bypass terminal.
NOTE Install rectifier input lugs using M12
50mm bolts from the single-feed kit.
Tie Wraps (3 places)
Front
Figure 1. 9395 650–825 kVA UPS Single-Feed Kit