Setup and Starting—Initial Configuration
6 S611 Soft Starter MN03901003E—January 2012 www.eaton.com
Setup and Starting—Initial Configuration
1. The S611 Operation and Protection parameters may be
edited when 120 Vac control power is applied to 120 Vac
supply (TB1). Mains power is not required to edit and
save Operation and/or Protection parameters.
2. If any 120 Vac power source other than the normal system
control power source is used to power the control circuit to
edit parameters, connections must be made in compliance
with all local, state, and national electrical codes.
3. To setup the S611 Operating parameters (Operation
mode), perform the following steps:
a. Enter motor FLA.
b. Enter motor rated voltage.
c. Select start method if required (default = voltage
ramp, or pump start).
d. Enter Start time from table on Page 7 (default =
20 seconds).
e. Enter initial torque from table on Page 7 (default =
45%).
f. Enter Stop time, Kick Start time, and Kick Start
torque if desired (default = 0).
4. Application Notes
Adjust Initial Torque for smooth start, motor rotation
should begin within 2 seconds.
If Stall Faults occur at the end of the ramp time, increase
Initial Torque, Kick Start Torque and Time and/or Soft
Start Time to achieve bypass before the Soft Start time
elapses. Verify that the motor is not overloaded.
After suitable performance has been achieved with either
method, determine the starting time to bypass and set
Soft Start Time at 1.25 times this time. For example, if it
takes 10 seconds to accelerate the motor and go into
bypass, set the Soft Start Time for 12.5 seconds.
5. In the Protection Mode, set the Protection parameters
to the desired values. Refer to table on Page 7.
6. For optional advanced configuration parameters refer to
the user manual.
Operating Parameters
Notes
For the device with pump option, the default value is 2 for pump start.
Operating Parameter Units Min Max Default Notes
Motor FLA Amps Motor FLA parameter must be set to
motor nameplate FLA to achieve
proper overload protection
Frame Size A–52 26 52 26
Frame Size A–65 32.5 65 32.5
Frame Size A–77 38.5 77 38.5
Frame Size B–99 48 99 48
Frame Size B–125 62.5 125 62.5
Frame Size C–156 78 156 78
Frame Size C–180 90 180 90
Frame Size D–242 120 242 120
Frame Size E–302 151 302 151
Frame Size E–361 180.5 361 180.5
Frame Size F–414 207 414 207
Motor rated voltage Volts 200 600 480
Start method 0 2 0
0 = Voltage ramp
1 = Current limit
2 = Pump start (option)
Start time
Seconds 0.5 180 20
Initial torque % 0 100 45
Stop time Seconds 0 60 0
Kick start time Seconds 0 2 0
Kick start torque % 0 100 0
Auto reset mode 0 1 0
0 = Manual
1 = Auto
Advanced config Refer to User Manual, Publication No.
MN03902011E