Troubleshooting
8 S611 Soft Starter MN03901003E—January 2012 www.eaton.com
Troubleshooting
S611 Fault Codes
Code Fault Condition Solution
3
Watchdog Firmware fault
5 Internal Memory Internal FRam memory error Component failure on printed circuit board
Contact EatonCare for service
6 User Interface Communications
Failure
Communications to UI have been
interrupted
Possible hardware failure
Firmware is not communicating internally
Cycle 120 Vac control voltage power to attempt to
clear problem
7 Internal Program Memory Corrupted firmware or memory
Flash CRC
Cycle 120 Vac control power to the S611
Contact EatonCare for service
8 Voltage Zero Cross Lost Mains voltage lost
Phase L1 or L3 lost
Load disconnected
Restore mains or lost phases
Verify that the load is connected and any disconnect
devices are properly engaged
Contact EatonCare for service
9 Communications Loss Port A Communications to a remote network
controller was lost during run cycle
Device disconnected
Connection lost
Reattach network controller, verify that the unit is
recognized by the system controller
10 Communications Loss Port B Communications to a remote network
controller was lost during run cycle
Device disconnected
Connection lost
Reattach network controller, verify that the unit is
recognized by the system controller
Comms Port B adapter module failed or disconnected
15 Power Pole Over Temperature SCR temperature is above limits
Operating environment above specified
maximum temperature
Ventilation holes blocked
Fans are not operational
Starts/hour exceed specifications
Sensor failure on power pole
Bypass contactor(s) failed to close
Ventilate to specified maximum temperatures
Clear obstructions
Verify fans are operational
Verify system is not exceeding the specified
maximum starts per hour
Verify bypass contacts are closing at the end of ramp
time
Reduce excessive cabinet temperature
16 Bypass Failure Internal bypass contactor(s) not closed
and/or electrically sealed after ramp time
Contactor(s) opened in bypass
Verify all bypass contactor(s) close (audible noise)
Verify all bypass contactor(s) not opening during run
cycle due to excessive vibration and/or shock
Reduce levels of vibration and/or shock
Verify control power and wire size meet
specifications
Verify that the control power supply meets the
120 Vac voltage and current requirements of the
IT. soft starter
17 SCR Not Firing SCR is not conducting when gated
Incoming phase lost
Special application—undersized or high
impedance motor
Load disconnected
SCR failure
Re-apply lost phase
Review S611 application
Circuitry damaged by megger testing
Contact EatonCare for service