Troubleshooting
S611 Soft Starter MN03901003E—January 2012 www.eaton.com 9
S611 Fault Codes, continued
Note
Shorted SCRs are the most common mode of SCR failure. With power completely removed from the unit, measure the resistance of each pole, line to load.
If the resistance is near zero (less than 5 ohms), it is most likely that the SCR is shorted. Resistance of a serviceable SCR is approximately 10k ohms.
Resistance typically moves to a lower value as the SCR ages. This feature may be disabled (not recommended).
Code Fault Condition Solution
18 Shorted SCR
SCR is shorted
Internal bypass contactor welded shut
No load on the SCRs when START
command is issued
Test resistance of each phase
Contact EatonCare for service
19 Instantaneous Overcurrent Excessive starting current
Excessive load
Reduce starting load
Increase soft starter capacity (be sure model ratings
can handle current demands)
20 Overload Motor overloaded for an extended
period of time
Thermal memory is over 100%
Reduce the motor’s load
Verify the
Overld Trip FLA and/or Ovrld Trip Class for
proper adjustment
Note: Exceeding nameplate ratings will shorten
equipment life
Fault during motor start: Verify system is not
exceeding the specified maximum starts per hour
Increase the initial torque and/or reduce ramp time
to bring the motor up to speed faster
Increase Trip Class setting (5–30 maximum) and/or
reduce ramp time setting
21 Mains AC Voltage Loss Fuses or breaker open
Disconnect open
Replace fuses, close disconnect, or reset breaker
22 Under Voltage Incoming AC line voltage below trip
threshold
Incorrect mains supply voltage
Connect to correct supply voltage
Verify that mains voltage is within acceptable values
Verify
Motor Rated Voltage in the Operation mode is
set to the correct value
23 Over Voltage Incoming AC line voltage above trip
threshold
Incorrect mains supply voltage
Connect to correct supply voltage
Verify
Motor Rated Voltage in the Operation mode is
set to correct value
24 Phase Reversal Incoming line phase rotation sequence
opposite of device setting
Single-phase missing and/or open fuse
or breaker
Set Phase Sequence to match incoming sequence OR
Exchange two incoming mains phases
Verify that all circuit breakers are closed or fuses are
serviceable
25 Start Stall Motor not at rated RPM at end of start
ramp time and/or current is in excess of
trip threshold
Bypass contactors not closed at the end
of the start time (start current low/ramp
time short)
Lengthen Soft Start Time and/or increase Initial
Torque
in the Operations mode
Increase trip threshold
Loads that are heavily loaded (high inertia) during a
start such as fans will often need an initial torque
setting much greater than the factory default
Set
Kick Start parameters
27 SCR Overcurrent Excessive SCR current during the start
ramp
Only active when Stall Fault is disabled
Increase Soft Start Time and/or Initial Torque
parameters in
Operation mode
Reduce starting load
Verify S611 is properly rated for current
28 Under Load Loss of motor load
Trip threshold set too high
Excessive current fluctuation during
operation
Inspect for failed motor coupling or pump cavitation
Reduce trip threshold
Increase trip delay time to ride through transient load
changes