Troubleshooting
10 S611 Soft Starter MN03901003E—January 2012 www.eaton.com
S611 Fault Codes, continued
Note: All mains and control power connections must be completed and voltage applied prior
to a START command. Failure to make all connections will result in one or more faults.
All isolation and/or reversing contactors must be staged prior to any START commands.
Manipulating contactors after the START command will result in one or more faults.
Code Fault Condition Solution
29
Current Unbalance The current imbalance of the incoming
phases exceeds the trip threshold
Correct imbalance problem with mains
Increase the
Current Imbalance parameters
Disable the fault if the other issues cannot be
resolved
30 Current Phase Loss Incoming phase disconnected
Open fuse or breaker
Phase imbalance exceeds specifications
or trip parameter
Severe voltage phase imbalance
Repair broken connection
Replace fuse
Inspect system for phase imbalance conditions
31 Voltage Phase Imbalance The voltage imbalance of the incoming
phases exceeds the trip threshold
Correct imbalance problem with mains
Increase the
Voltage Fault Imbalance parameters
Disable the fault if the other issues cannot be resolved
33 Jam Soft starter in bypass: Motor below rated
RPM and/or current exceeds 3 x motor
FLA
Remove obstruction
Verify proper FLA setting in Operation mode
Jam fault can be disabled if trips occur during normal
operation (Overcurrent fault will provide protection at
a higher current threshold of 4 x catalog FLA)
34 Contactor Overcurrent Only active in bypass if the jam fault is
disabled
Current exceeds the fault threshold of
4 x catalog FLA
Remove obstruction in motor drive train
Verify S611 is properly sized for the application
35 Missing Temp Sensor Temperature sensor failure
Internal connection failure
Internal hardware failure (sensor and/or cable)
Note: Disabling this feature (Temp Sense fault in
Protection menu) will remove protection from
excessive temperature exposure (not recommended)
Not field repairable, contact Eaton Support
* Cannot RESET fault Fault condition still exists
Soft starter has not received RESET
signal
Troubleshoot fault and correct defective condition
Attempt alternate methods of RESET
NC No communication Firmware not programmed, firmware
corrupted
Contact EatonCare for service