6 Battery Upgrade Instructions for 9355 (20–30 kVA) —Rev 01
Figure 8. Remove the Old Two-Row Battery Tray
8. Slide two new single-row trays in place of the tray that was removed. The two new single-row trays are
now side-by-side with one old dual-row tray on the same shelf, forming two battery strings (see Figure 9).
Figure 9. Slide Two Single-Row Battery Trays into Place
9. Re-install the battery retaining bracket and secure using the two M5 bolts removed in Step 6(see
Figure 10).
10. Cut the tie wrap securing the UPS battery harness to the battery retaining bracket (see Figure 10).
Battery Upgrade Procedure