Page 50 (60) Motor Pump Enhanced Protection Application SV9000
6.2.11 Group 12, Digital Output Parameters
12.1 Digital output function
Setting value Signal content
0 = Not used Out of operation
Digital output DO1 sinks the current and programmable relay (RO1, RO2) is activated when:
1 = Ready The frequency converter is ready to operate
2 = Run The frequency converter operates (motor is running)
3 = Fault A fault trip has occurred
4 = Fault inverted A fault trip has not occurred
5 = SV9000 overheat warning The heat-sink temperature exceeds +70
o
C
6 = External fault or warning Fault or warning depending on parameter 7.2
7 = Reference fault or warning Fault or warning depending on parameter 7.1 -
if analog reference is 4 – 20 mA and signal is <4mA
8 = Warning Always if a warning exists
9 = Reversed The reverse command has been selected
10 = Jogging speed Jogging speed has been selected with digital input
11 = At speed The output frequency has reached the set reference
12 = Motor regulator activated Overvoltage or overcurrent regulator was activated
13 = Output frequency supervision 1 The output frequency goes outside of the set supervision.
Low limit/ High limit (par. 3.6 and 3.7)
14 = Output frequency supervision 2 The output frequency goes outside of the set supervision.
Low limit/ High limit (par. 3.8 and 3.9)
15 = Torque limit supervision The motor torque goes outside of the set supervision.
Low limit/ High limit (par. 3.10 and 3.11)
16 = Reference limit supervision Reference goes outside of the set supervision.
Low limit/ High limit (par. 3.12 and 3.13)
17 = External brake control External brake ON/OFF control with programmable delay (par 3.14 and 3.15)
18 = Control from I/O terminals External control mode selected with progr. push-button #2
19 = Temperature Limit Supervision Temperature on frequency converter goes outside the temperature limit
supervision set supervision limits (par. 3.16 and 3.17)
20 = Unrequested rotation direction Rotation direction of the motor shaft is different from the requested one
21 = External brake control inverted External brake ON/OFF control (par. 3.14 and 3.15), output active when brake
control is OFF
22 = Thermistor fault or warning The terminator input of option board indicates overtemperature. Fault or
warning depending on parameter 7.19
23 = Hot Motor Winding Fault A hot motor winding fault has tripped
24 = Hot Motor Bearing Fault A hot motor bearing fault has tripped
25 = Seal Seat Detection Fault A seal leak detection fault has tripped
26 = High Vibration Fault A high vibration fault has tripped
Parameter Settings Descriptions
27 = Warn Flash
Output will toggle in Flash mode
Selections 0 – 27 from Parameter Setting Descriptions table below.
12.2 Relay output function
Selections 0 – 27 from Parameter Setting Descriptions table below.
12.3 Relay 2 output function
Selections 0 – 27 from Parameter Setting Descriptions table below.
12.4 Relay 3 output function
12.5 Relay 4 output function
Selections 0 – 27 from Parameter Setting Descriptions table below.
12.6 Relay 5 output function
Selections 0 – 27 from Parameter Setting Descriptions table below.
Selections 0 – 27 from Parameter Setting Descriptions table below.