SVX9000 Drives    MN04003009E—November 2011    www.eaton.com 14
STEP 4 (Continued)
Protections — M1 
➔
 
G1.7
Code Parameter Min. Max. Unit Default Cust ID Note
P1.7.2 Reference fault 
frequency
0.00 Par. 
1.1.2
Hz 0.00 728
P1.7.3 Response to 
external fault
0 3 2 701 0 = No response
1 = Warning
2 = Fault.stop 
acc. to 1.4.7
3 = Fault.stop 
by coasting
P1.7.4 Input phase 
supervision
0 3 3 730
P1.7.5 Response to 
undervoltage 
fault
1 3 0 727
P1.7.6 Output phase 
supervision
0 3 2 702
P1.7.7 Earth fault 
protection
0 3 2 703
P1.7.8 Thermal 
protection of 
the motor
0 3 2 704
P1.7.9 Motor ambient 
temperature 
factor
-100.0 100.0 % 0.0 705
P1.7.10 Motor cooling 
factor at zero 
speed
0.0 150.0 % 40.0 706
P1.7.11 Motor thermal 
time constant
1 200 min 45 707
P1.7.12 Motor duty 
cycle
0 100 % 100 708
P1.7.13 Stall protection 0 3 0 709
0 = No response
1 = Warning
2 = Fault.stop 
acc. to 1.4.7
3 = Fault.stop 
by coasting
P1.7.14 Stall current 0.1 I
nMotor
 
x 2
AI
L
710
P1.7.15 Stall time limit 1.00 120.00 s 15.00 711
P1.7.16 Stall frequency 
limit
1.0 Par. 
1.1.2
Hz 25.0 712
P1.7.17 Underload 
protection
0 3 0 713 0 = No response
1 = Warning
2 = Fault.stop 
acc. to 1.4.7
3 = Fault.stop 
by coasting
P1.7.18 Field 
weakening area 
load
10 150 % 50 714
P1.7.19 Zero frequency 
load
5.0 150.0 % 10.0 715
P1.7.20 Underload 
protection time 
limit 
2 600 s 20 716
P1.7.21 Response to 
thermistor fault
0 3 2 732 0 = No response
1 = Warning
2 = Fault.stop 
acc. to 1.4.7
3 = Fault.stop 
by coasting
P1.7.22 Response to 
fieldbus fault
0 3 2 733 See P1.7.21
P1.7.23 Response to 
slot fault
0 3 2 734 See P1.7.21
P1.7.24 FB MCW Bit 15 0 2 0 771 0 = No action
1 = Fault low
2 = Fault high
MN04003009E.fm  Page 14  Wednesday, November 9, 2011  8:47 AM