15 SVX9000 Drives    MN04003009E—November 2011    www.eaton.com
STEP 4 (Continued)
Auto Restart Parameters — M1 
➔
 
G1.8
Keypad Control — M2
This menu provides the parameters for the setting of the keypad frequency 
reference, the selection of motor direction when in keypad operation, and 
when the STOP button is active.
Keypad Control Parameters — M2
Other Menus — M3 to M6
Menus M3 to M6 provide information on the Active Faults, Fault History, 
System Menu settings and the Expander Board setup. These menu items are 
explained in detail in Chapter 5 of the SVX9000 User Manual.
Code Parameter Min. Max. Unit Default Cust ID Note
P1.8.1 Wait time 0.10 10.00 s 0.50 717
P1.8.2 Trial time 0.00 60.00 s 30.00 718
P1.8.3 Start function 0 2 0 719 0 = Ramp
1 = Flying start
2 = According to 
par. 1.4.6
P1.8.4 Number of tries 
after 
undervoltage 
trip
0 10 0 720
P1.8.5 Number of tries 
after 
overvoltage 
trip
0 10 0 721
P1.8.6 Number of tries 
after 
overcurrent trip
0 3 0 722
P1.8.7 Number of tries 
after reference 
trip
0 10 0 723
P1.8.8 Number of tries 
after motor 
temperature 
fault trip
0 10 0 726
P1.8.9 Number of tries 
after external 
fault trip
0 10 0 725
P1.8.10 Number of tries 
after underload 
fault trip
0 10 0 738
Code Parameter Min. Max. Unit Default Cust ID Note
P2.1 Control place 0 3 0 1685 0 = Keypad L/R
1 = Local
2 = Remote
3 = I/O force
R2.1 Keypad 
reference
Par. 
1.1.1
Par. 
1.1.2
Hz
P2.3 Direction (on 
keypad)
0 1 0 123 0 = Forward
1 = Reverse
P2.4 Stop button 0 1 1 114 0
 = Limited 
function of 
Stop button
1 = Stop button 
always 
enabled
P2.5 Operate menu 
hide
0 1 0 1688 0 = No
1 = Yes
MN04003009E.fm  Page 15  Wednesday, November 9, 2011  8:47 AM