17 SVX9000 Drives    MN04003009E—November 2011    www.eaton.com
STEP 6
Monitoring Menu — M7
The Monitoring Menu items are meant for viewing parameter values during 
operation. Monitored values are updated every 0.3 sec. Monitored items are 
identified by item numbers V7.1 to V1.xx, where “xx” varies by application. 
The table below provides an example of the monitored values for the 
Standard application. 
Monitored parameters are not editable from this menu (See Parameter 
Menu [M1] to change parameter values). 
Monitoring Menu Items — Standard Application Example
Digital Inputs — DIN1, DIN2, DIN3 Status
Digital Inputs — DIN4, DIN5, DIN6 Status
Digital and Relay Outputs — DO1, RO1, RO2 Status
Multimonitor (V7.17)
This parameter allows the viewing and selection (if allowed by System 
menu item, P5.5.4) of three simultaneously monitored items from the 
Monitored Menu Items shown in the table above. Use the right arrow key to 
select the item to be modified and then the up or down arrow keys to select 
the new item. Press the ENTER key to accept the change.
Code Signal Name Unit Description
V7.1 Output 
Frequency
Hz Output frequency
V7.2 Frequency 
reference
Hz Frequency reference setting
V7.3 Motor speed rpm Calculated motor speed
V7.4 Motor current A Measured motor current
V7.5 Motor torque % Calculated torque based on nominal motor torque
V7.6 Motor power % Calculated power based on nominal motor power
V7.7 Motor voltage V Calculated motor voltage
V7.8 DC bus voltage V Measured DC-bus voltage
V7.9 Unit temperature °C Heatsink temperature
V7.10 Calculated motor 
temperature
°C Calculated motor temperature based on the 
motor nameplate information and the calculated 
motor load
V7.11 Analog Input 1 V Voltage input at Terminals AI1+ and GND
V7.12 Analog input 2 mA Current input at Terminals AI2+ and AI2-
V7.13 DIN1, DIN2, DIN3 — Digital input status (see figure below)
V7.14 DIN4, DIN5,DIN6 — Digital input status (see figure below)
V7.15 DO1, RO2, RO3 — Digital and relay output status (see figure below)
V7.16 Analog I
out
mA Current output at Terminals AO1+ and AO1-
V7.17 Multimonitor (See below)
V1.13
DIN1, DIN2, DIN3
OFF ON  OFF
V1.14
DIN4, DIN5, DIN6
ON OFF OFF
V1.15
DO1, RO1, RO2
OFF OFF ON