42 UPS 20-40 kVA, 230/400 V 50/60 Hz output
Users Guide
1025358
Revision D
Figure 23 Wiring diagram with SPM-30-2 and SPM-60-2
Power Fuse 1 Fuse 2* Cable A/B Cable C/D
20 kVA 35 A 63 A 10 mm² 16 mm²
30 kVA 50 A 100 A 10 mm² 35 mm²
40 kVA 80 A 125 A 25 mm² 50 mm²
60 kVA 100 A 200 A 35 mm² 95 mm²
Table 10 Recommended cables and fuses for the wiring diagram
(*These fuses are sized for capacity systems)