5
Installation
INSTRUCTION MANUAL MN050011EN August 2022 www.eaton.com
Step 3. Make sure that the device is de-energized.
Step 4. Pull connector X6 out from the female connector at
the top in order to disconnect the device from the
power supply.
Figure 9. Disconnecting the device from the
power supply
Connection terminals
Plug connector
X6: The required plug connector with push-in spring-cage
terminals FMC 1.5/4-ST-3.5 is included as standard with
the XN-332-5ETH-UMS. To use them, the conductor simply
needs to be slid into the appropriate contact.
In order to release the conductor, simply press on the
release mechanism, e.g., with a screwdriver, to pull out the
conductor from the corresponding contact.
Table 2. Connection specifications
Cable cross-sectional areas XN-332-…
0.39 inch (10 mm) Solid mm
2
0.2–1.5
0.39 inch (10 mm)
Flexible with uninsulated ferrule mm
2
0.2–1.5
0.39 inch (10 mm) Flexible with insulated ferrule mm
2
0.2–0.75
Ferrule d mm ≤ 2.8
AWG 24–16
Strip length mm 10
Figure 10. Ferrule with d2 = Maximum 2.8 mm
NOTICE
THE SPRING-CAGE TERMINALS CAN BE USED TO CONNECT
ULTRASONICALLY SPLICED (ULTRASONICALLY WELDED) WIRES.
4
RN
DC
LA
X1
FD
LA
X2
FD
LA
X3
FD
LA
X4
FD
LA
X5
FD
d Ød