EasyManua.ls Logo

Eaton XN300 - Connecting the Power Supply

Eaton XN300
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
Installation
INSTRUCTION MANUAL MN050011EN August 2022 www.eaton.com
Connecting the power supply
DANGER
IN SAFETY-RELEVANT APPLICATIONS, THE POWER SUPPLY
USED TO POWER THE XN300 SYSTEM MUST BE A PELV POWER
SUPPLY UNIT.
The two 24 V V+ terminals are internally connected to
each other (X6:
a
and
b
), as are the two 0 V GND terminals
(X6:
c
and
d
). Only one V+ and one 0 V terminal need to
be connected in order to power the gateway. The internally
connected terminals can be used to extend the 24 V and
0 V supply voltage connections. However, it is necessary
to make sure that a total current of 4 A is not exceeded
per terminal.
External 24 Vdc voltages can also be distributed
using an XN-322-4PS-20 power distribution module or
XN-322-18PD-P and XN-322-18PD-M field potential
distributor modules.
The plug connector with push-in spring-cage terminal
FMC 1.5/4-ST-3.5 is included in the scope of supply.
Figure 11. Connection of power supply
a
24 V V+
b
24 V V+
c
0 V GND
d
0 V GND
The device must be powered with a galvanically isolated
power supply with a rated voltage of 24 Vdc. A ULT 249
fuse (maximum 4 A) must be installed between the power
supply and the device.
Figure 12. Wiring the power supply
0.12 inch (3.0 mm)
F1
X6
U
e
= 24 Vdc
(18–30 Vdc SELV)
I
e
0.2 A
V+
V+
0 V
0 V
0 V
24 Vdc
F1
F1 4 A