8
Appendix
INSTRUCTION MANUAL MN050011EN August 2022 www.eaton.com
Technical data
Ambient conditions
Description Specification
Storage temperature –20 to +85 °C
Operating ambient temperature 0 to +55 °C
Humidity 0–95 %, noncondensing
EMC interference immunity As per EN 61000-6-2 (industrial environment)
EMC emitted interference As per EN 61000-6-4 (industrial environment)
Vibration resistance EN 60068-2-6 3.5 mm of 5–8.4 Hz
1 g of 8.4–150 Hz
Mechanical shock resistance EN 60068-2-27 15 g
Protection type EN 60529 IP20
Power supply
Specifications for connection to supply voltage
Specifications for connection to supply voltage Ue V 18–30 V
a
DC
Residual ripple of input voltage % ≤ 5
Protection against polarity reversal No
Overload proof Yes
Supply current X6 (typ.) 200 mA
a
The device must be powered with a galvanically isolated power supply
with a rated voltage of 24 Vdc. A UL 249 fuse (maximum 4 A) must be
installed between the power supply and the end device.
Cable cross-sections
Cable cross-sectional areas XN-332-…
0.39 inch (10 mm) Solid mm
2
0.2–1.5
0.39 inch (10 mm)
Flexible with
uninsulated ferrule
mm
2
0.2–1.5
0.39 inch (10 mm) Flexible with
insulated ferrule
mm
2
0.2–0.75
Ferrule d mm ≤ 2.8
AWG 24–16
Strip length mm 10
Additional information
General XN-332-…
Imprintable label MF 10/5 CABUR MC NE WS (Weidmüller)
Further reading and links
For more information on additional devices and modules,
please visit the following links.
Product information
For up-to-date information, please consult the product page:
Eaton.de/xn300
Download Center—documentation
You can find the documents on the Download Center
documentation page by entering the document name.
http://www.eaton.eu/documentation
File type Title Designation
Mounting instruction XN-332-5ETH-UMS IL050026ZU
Mounting instruction XN-312-GW-CAN IL050017ZU
Mounting instruction XN-312-GW-EC IL050025ZU
Mounting instruction XC300 IL050018ZU
Manual XN-312-GW-CAN MN050003
Manual XN-312-GW-EC MN050010
Manual XN300 slice modules MN050002
Manual XC300 MN050005
d Ød