GOLD SERIES GTC116 TRANSMITTER
a measurable difference!
EBTRON
IG_GTC116_R3A
Function
Address
Type
Units Description
Range/Value
2
10001
boolean
Trouble
Status
0:OK,
1:Trbl
4
30001-30002
float FPM
Avera
g
e
Airflow
0to
15,000
4
30003-30004
float °F
Avera
g
e
Tem
p
erature
-20 to
160
4
30005
word
Numbe
r
o
f
Inserts
0to
16
4
30006
word
0
4
30007
word
Alarm
Status
0: No
alarm
1: High
Alarm
2: Low
Alarm
3:
Both
4
30008
word
Connecto
r
C1
Sensors
0 to
8
4
30009
word
Connecto
r
C2
Sensors
0 to
8
4
30010
word
Connecto
r
C3
Sensors
0 to
8
4
30011
word
Connecto
r
C4
Sensors
0 to
8
4
30012-30043
float
FPM
Airflow
Flow
Traverse
0 to
15,000
30012-30013
Insert 1
Flow
30042-30043
Insert 16
Flow
4
30044-30075
float
°F
Tem
p
erature Traverse
-20 to
160
30044-30045
Insert 1
Tem
p
30074-30075
Insert 16
Tem
p
4
30076-30077
float
Sq.Ft. Area
0 to
100
4
300202
word
Float word
order
0: high word
first;
1: low word
first
Analog Values
AV, 1 Area sq.ft.
AV, 2 Traverse Data Status 0=None, 1=Flow,
2=Temp, 3=Both
AV, 3 Flow Traverse FPM
AV, 18 Flow Traverse FPM
AV, 19 Temperature Traverse °F
AV, 34 Temperature Traverse °F
Notes:
1. Flow and Temp traverse must be enabled through AV2.
2. User Executed Services Supported:
Subscribe COV, Read Property, Write Property,
Device Communication Control, Who-Is.
Analog Inputs
Type, ID Name Default
Units
Device GTC116
AI, 1 Average Flow CFM
AI, 2 Average Temperature °F
AI, 3 Alarm Status 0: No alarm,
1: High Alarm,
2: Low Alarm,
3: Both
Table2. GTC116BACnetObjectsList
Table3. GTC116ModbusRegisterMap
BACnetMS/TP