1 GTC116TRANSMITTERINSTALLATION
TheGTC116transmitterisdesignedforuseinanenvironmentbetween‐20°Fto120°F(‐28.8°Cto48.8°C)where
itwillnotbeexposedtorainorsnow.Installtransmitteruprightandinafieldaccessiblelocation.Theenclosure
accepts1/2in.(12.7mm)electricalfittingsfor
signalandpowerwiringatbothsidesatthetopoftheenclosure.
Locatethetransmittersothattheconnectingcablesfromallofthesensorprobeswillreachthereceptaclesonthe
bottomofthetransmitterenclosure.
Inlocationsexposedtodirectrainand/orsnow,thetransmittermustbe
enclosedinaNEMA4
enclosure.
Leaveunobstructedspaceofatleast9in.(228.6mm)above,2in.(50.8mm)toeachsideand3.5
in.(88.9mm)belowthetransmittertoallowforcoverremoval,sensorconnectionsandheat
dissipation.
Locatethetransmitterinalocationthatcanbereached
byallconnectingcablesfromthesensor
probes.
Donotdrillintothetransmitterenclosuresincemetalshavingscoulddamagetheelectronics.
1.1 GTC116MechanicalDimensions
Figure1.GTC116MechanicalDimensions
!
!
!
!
2) IF UNIT HAS 2 PROBE CONNECTIONS THEN IT IS A TYPE "A" UNIT.
IF UNIT HAS 4 PROBE CONNECTIONS THEN IT IS A TYPE "B" UNIT.
NOTES:
1) MEASUREMENTS IN BRACKETS ARE IN MILLIMETERS.
Ø.88
[Ø22.23 mm]
6.69
[169.86 mm]
5.94
[150.81 mm]
1.38
[34.93 mm]
SEE NOTE 2
1.56
[39.67 mm]
Ø.19
[Ø4.76 mm]
2.50
[63.50 mm]
7.94
[201.55 mm]
.38
[9.53 mm]
7.19
[182.55 mm]
8.69
[220.73 mm]
.75
[19.05 mm]
5.19
[131.76 mm]
PROVIDE 3.5 INCH MINIMUM CLEARANCE AT
BOTTOM FOR CONNECTOR ACCESS.
PROVIDE 9 INCH MINIMUM CLEARANCE AT TOP
FOR COVER ACCESS (SLIDE UP TO REMOVE).
PROVIDE 2 INCH MINIMUM CLEARANCE AT BOTH
SIDES OF ENCLOSURE
1.38
[35.05 mm]
[O4.83 mm]
O.19
[182.63 mm]
[201.68 mm]
[9.65 mm]
[39.62 mm]
[131.83 mm]
[150.88 mm]
[169.93 mm]
[O22.35 mm]
O.88