GOLD SERIES GTC116 TRANSMITTER
a measurable difference!
EBTRON
IG_GTC116_R3A
5.7 GTC116‐AnalogOutp utTypeSelectionandSetup
TheanalogoutputsignaltypeatAO1(OUT1,airflow)andAO2(OUT2,temperature/alarm)canbesetformAor
VDCoutputbysettingswitchesSW1/SW2(Figures6and7)and
byselectingthe4 20mA,05VDCor010VDC
rangesintheANALOGOUTsubmenuoptions*AO1RNGE=/*AO2RNGE= settings.Thetransmitterisshipped
fromthefactorywithSW1/SW2andSetupmenuoptions*AO1RNGE=and*AO2RNGE=setfor420mA.
5.7.1 GTC116‐ConvertingAnalogOutputSignalValuestoAirflowandTemperature
Table7listsspecificconversionequationsforanalogvoltageorcurrentoutputoptions.
5.7.2 GTC116‐AO1/AO2OUTPUTTEST‐SendingaTestOutputSignaltotheHostControl
System
Atestoutputsignalbetween0 and100%ofthefullscaleoutput(420mAor05VDC/010VDC)canbeprovided
bytheGTC116transmitterto verifyproper conversionof theoutput signals fromthe transmitterat thehost
control system. Tosetafixedoutputsignalforairflow
andtemperature,navigatetotheOUTPUTTESTsubmenuin
theTOOLSmenu. OUT1andOUT2testsareindependentlyaccessed,andtheoutputwillmaintainthe%selected
untilthe“ESC”buttonispressedandnormaloperationresumes.
Table7.GTC116ConvertingAnalogOutputValuestoAirflow/Temperature
TO CONVERT TO
Airflow (FPM, MPS) Output Voltage/10 x FS1 Output Voltage/5 x FS1 (Output Current-4)/16 x FS1
Airflow (CFM) Area (SQF) x Output/10 x FS1 Area (SQF) x Output/5 x FS1 Area (SQF) x (Output - 4)/16 x FS1
Airflow (LPS) Area (SQM) x Output/10 x FS1 x 1000 Area (SQM) x Output/5 x FS1 x 1000 Area (SQM) x (Output - 4)/16 x FS1 x 1000
TO CONVERT TO
Airflow (CFM, LPS) Output Voltage/10 x FS1 Output Voltage/5 x FS1 (Output Current - 4)/16 x FS1
TO CONVERT TO
Temp (°F,°C) Output Voltage/10 x (FS2-MS2) +MS2 Output Voltage/5 x (FS2-MS2) +MS2 (Output Current - 4)/16 x (FS2-MS2) +MS2
NOTES:
FS1 is AO1 full scale analog output value from ANALOG OUT MENU.
FS2 is AO2 full scale analog output value from ANALOG OUT MENU.
MS2 is AO2 minimum scale analog output value from ANALOG OUT MENU.
0-10 VDC 0-5 VDC 4-20 mA
ANALOG OUTPUT SCALING AND TYPE
0-10 VDC 0-5 VDC 4-20 mA
When OUTPUT 2 is Configured as Temperature (°F,°C):
ANALOG OUTPUT SCALING AND TYPE
0-10 VDC 0-5 VDC 4-20 mA
ANALOG OUTPUT SCALING AND TYPE
When OUTPUT 1 is Configured as Linear Airflow (FPM, MPS):
When OUTPUT 1 is Configured as Volumetric Airflow (CFM, LPS):