and set temperature before the system calls
for heat. A smaller dierence means shorter
cycle times, whereas a larger dierence results
in longer cycle times. The temperature range
is adjustable from 0 to 3 °F (-17.5 to 26.5 °C) in
0.5°F (0.3°C) increments.
Heat Dissipation Time The amount of time
the fan will run after the heat set point has
been reached and the call for heat has been
turned o. Running the fan for a period of
time allows for any heated air left in the ducts
to circulate throughout the home. The time is
adjustable from 0 to 900 seconds. The default
value is 30 seconds.
Cool Dierential Temp The minimum
dierence between the current temperature
and set temperature before the system calls
for cool. A smaller dierence means shorter
cycle times, whereas a larger dierence results
in longer cycle times. The temperature range
is adjustable from 0 to 3 °F (0.3 to 1.7 °C) in
0.5°F (0.3°C) increments.
Cool Dissipation Time The amount of time
the fan will run after the cool has been turned
o. Running the fan for a period of time allows
for any cooled air left in the ducts to circulate
throughout the home. The time is adjustable
from 0 to 900 seconds. The default value is 30
seconds.
Advanced Settings
These options customize how long each stage
will run before the next stage turns on. You may
also program when a particular stage is turned
on based on the temperature delta between the
set temperature and the current temperature.
28