6.3.3.4 I value (KI)
I value indicates the additional compensation signal based on the percentage of error allowance. As
the value increase, it is more likely to cause hunting. As the value decreases, the positioner will move
slower to the target position.
6.3.3.5 P_ (KP_), D_(Kd_) , I_(KI_) values
P_, D_, and I_ values’ are principly the same as the P, D, and I values, but these values will be
activated when the error percentage is within 1%.
6.3.4 Hand Calibration Mode (HAND CAL)
The positioner can be manually calibrated by entering into Hand Calibration Mode.
6.3.4.1 Zero-Point (PV_ZERO) and End-Point (PV_END) for Valves
PZ_ZERO adjusts the zero point of the valve, and PV_END adjusts the end point of the valve.
<ENTER>
<DOWN>
3 times
<ENTER>
<UP><DOWN>
<ESC>
3 times
<ENTER>
<ENTER>
6 seconds
<DOWN>
3 times
<ENTER>
<ENTER>
<UP>/<DOWN>
<ESC>
Zero Adjustment
<ENTER>
<DOWN>
<ENTER>
<UP>/<DOWN>
End Adjustment <ENTER>
<ESC>