Installation and Operating manual
Econ
®
Series 3300 Smart Valve Positioner www.eriks.com
Rev. 3 – January 22, 2019
32
Erro
Error code or warning message.
VALUE I
Current I value
ABS
Absolute resistance value.
7 Error and Warning Codes
7.1 Error codes
Code Description and Cause
MT ERR L
Ø Positioner is improperly installed.
Ø Positioner is not parallel to the
ground at 50% point. Lever is at
lower position than actual 50% point.
Ø Re-install the positioner.
Ø Ensure the feedback lever does
not touch the lever stopper at 0%
and 100%.
MT ERR H
Ø Positioner is improperly installed.
Ø Positioner is not parallel to the
ground at 50% point. Lever is at
higher position than actual 50%
point.
Ø Re-install the positioner.
Ø Ensure the feedback leer does
not touch the lever stopper at 0%
and 100%.
CHK AIR
Ø Valve does not operate when
positioner receive “Full Open” signal
during the auto calibration.
Ø Check supply pressure level.
RNG ERR
Ø Operating angle is too small due to
improper positioner installation.
Ø Adjust bracket so the positioner
can be mounted closer to
actuator.
C
Error of 10% or more persists more than 1
minute.
Ø No valve movement.
Ø High level of valve friction
Ø Changes in setting pressure of actuator.
Ø Perform AUTO HF / BIAS calibration.
Ø Check setting pressure of actuator.
D
I-value reaches at maximum or minimum
limit.
Ø Changes in valve friction.
Ø Changes in setting pressure of actuator.
Ø Perform AUTO HF calibration.
Ø Check setting pressure of actuator.