7.2 Warning codes
Code
Description Action
B
Ø Pv Span – Pv Zero range is below 500.
Ø The angle of feedback lever is too small.
Ø Re-install the positioner.
Ø Ensure the
touch the lever stopper at 0% and
100%.
Ø After re-installation, perform AUTO1.
F
Ø F
ull open/close elapsed time is less
than 1 second.
Ø Actuator size is too small.
Ø Use variable orifice.
Ø Use larger actuator.
G
Ø Pv is below 100.
Ø The angle of feedback lever is too large.
Ø Re-install the positioner.
Ø
Ensure the feedback lever does not
touch the lever stopper at 0% and
100%.
Ø After re-installation, perform AUTO1
H
Ø Pv is over 4000.
Ø The angle of feedback lever is too large.
Ø Re-install the positioner.
Ø
Ensure the feedback lever does not
touch the lever stopper at 0% and
100%.
Ø After re-installation, perform AUTO1
.