EasyManua.ls Logo

Econ 3300 Series - Product Specification

Econ 3300 Series
35 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...



Installation and Operating manual
Econ
®
Series 3300 Smart Valve Positioner www.eriks.com
Rev. 3 – January 22, 2019
8
2.4 Product Specification
Figure
3301
3302
3303
3304
Motion type
Linea
r
Acting Type
Single
Double
Single
Double
Input Signal
4~20mA DC
Min. Current Signal
3.2mA(Standard), 3.8mA(
HART
®
Included)
Supply Pressure
0.14~0.7 MPa (1.4~7 bar)
Stroke
10~150 mm
0~90°
Impedance
Max.45
0
@ 20mA DC
Air Connection
1/4” NPT
Gauge Connection
1/8” NPT
Conduit Entry
½” NPT with gland
for 8 mm cable
Protection Grade
IP66
Explosion Proof
ATEX,
Ex ia IIC T5/T6 Gb, Ex iaD IIIC T100
/T85
Db, IP66
Ambient Temp.
Operating Temp. :-30~85
Line
arity
±0.5% F.S.
Hysteresis
0.5% F.S.
Sensitivity
±0.2% F.S
Repeatability
±0.3% F.S
Flow Capacity
70 LPM (Sup.=0.14 MPa)
Air Consumption
Below 2 LPM (sup = 0.14 MPa), Below 3 LPM (sup = 0.7MPa)
Output Characteristic
Linear, Quick Open, EQ%, User Set
(16 point)
Vibration
No Resonance up to 100Hz @ 6G
Humidity
5-95% RH @ 40
Communication
HART
®
Communication
Feedback Signal
4~20mA (DC 10~30V)
Material
Aluminum Die
-
casting
Weight
2.0kg
Painting
Epoxy Powder Coating
Tested under ambient temperature of 20’C, absolute pressure of 760mmHg, and humidity of 65%.

Other manuals for Econ 3300 Series