Series 3300 Smart Valve Positioner www.eriks.com
Rev. 3 – January 22, 2019
30
6.3.5.6 Split Range Mode (SPLIT)
The valve can be operated by split range control – 4~12mA or 12~20mA.
6.3.5.7 Custom Zero Setting Mode (CST ZERO)
Custom Zero Setting Mode allows the user to set any specific point as zero position. For example,
the zero point can be set at input signal of 7mA.
6.3.5.8 Custom End Setting Mode (CST ENd)
Custom End Setting Mode allows the user to set any specific point as end position. For example,
the end point can be set at input signal of 11mA. The difference between zero and end point
must be greater or equal to 4mA.