21
INSTRUCTION MANUAL ECOSOFT
®
MEDIA SYSTEMS
Model range
Model
Overall dimensions, m
(width × depth × height)
Nominal ow rate, m
3
/h
Quantity of media, L
Consumption of water
per regeneration, m
3
Required ow capacity,
m
3
/h
1
FP-1035 0,3×0,3×1,1 0,6 28,3 0,3-0,5 1,2
FP-1054 0,3×0,3×1,6 0,6 28,3 0,3-0,5 1,2
FP-1252 0,4×0,4×1,6 0,9 56,6 0,5-0,7 1,7
FP-1354 0,4×0,4×1,6 1,0 56,6 0,5-0,8 2,0
FP-1465 0,4×0,4×1,9 1,2 84,9 0,6-0,9 2,3
FP-1665 0,5×0,5×1,9 1,6 113,2 0,8-1,2 3,0
FP-2162 0,6×0,6×2,0 2,6 141,5 1,2-1,8 4,5
1
supply water ow rate required for proper regeneration of system
Ecosoft FP
®
ltration systems
Requirements and limitations
Installation room
Ambient temperature +5°C…+40°C
Relative humidity ≤80%
Operating environment
indoor; free of corrosive vapors, airborne dust,
and brous matter; sheltered from weather
and direct sunlight
Power supply
Electrical rating 230 V, 50 Hz (EU adapter)
Power 6 VA
Water supply
Pressure 2-6 bar (30-90 psi)
Water temperature +4°C…+30°C
Prelter rating 100 μm