5
ENG
CONTROL VALVE PROGRAMMING AND COVER DRAWING MANUAL
This manual is the intellectual property of Ecoso. Copying and reprinng is prohibited. © 2021
OEM GENERAL PROGRAMMING INSTRUCTIONS
The control valve’s unique design and electronics allows the OEM to select AUTO or MANUAL mode for programming.
Cycles can also be fine-tuned when mode is set to AUTO.
Table 1 – Program Parameters with Mode set to “AUTO SETUP”
System Type Media
Volume (L)
So�ening
Capacity
(meq/l)
So�ening
Capacity
(PPM or dH)
BW (min)
Down ow
only
Brine Draw
(min)
2
nd
BW
(min)
Rinse
(min)
Fill (kg)
ECOMIX 8 5.6 0.28 10 45 1 5 0.8
ECOMIX 12 8.4 0.42 10 45 1 5 1.2
ECOMIX 18 12.6 0.62 10 45 1 10 1.8
ECOMIX 25 17.5 0.86 10 60 1 10 2.5
ECOMIX 37 25.9 1.28 15 60 1 10 3.7
ECOMIX 50 35.0 1.74 15 60 1 10 5.0
ECOMIX 62 43.4 2.16 15 60 1 10 6.2
ECOMIX 75 52.5 2.62 15 60 1 10 7.5
ECOMIX 100 70.0 3.50 15 60 1 10 10.0
ECOMIX 125 87.5 4.36 15 60 1 10 12.5
SOFTENER 8 9.6 0.48 10 45 1 5 0.8
SOFTENER 12 14.4 0.72 10 45 1 5 1.2
SOFTENER 18 21.6 1.08 10 45 1 10 1.8
SOFTENER 25 30.0 1.50 10 60 1 10 2.5
SOFTENER 37 44.4 2.22 10 60 1 10 3.7
SOFTENER 50 60.0 3.00 10 60 1 10 5.0
SOFTENER 62 74.4 3.72 10 60 1 10 6.2
SOFTENER 75 90.0 4.50 10 60 1 10 7.5
SOFTENER 100 120.0 6.00 10 60 1 10 10.0
SOFTENER 125 150.0 7.50 10 60 1 10 12.5
Table 2 – CYCLE SEQUENCE with Mode set to “AUTO SETUP”
*lliFlliF*WBesniRWBwarD*esniRWBecivreSlliFepyT
SOFTENING, DOWNFLOW, POST FILL
X X X X X
SOFTENING, DOWNFLOW, PRE-FILL
X 240 X X X X 0:05
SOFTENING, UPFLOW, POST FILL
0:15 X X X X
SOFTENING, UPFLOW, PRE-FILL
X 240 0:15 X X X 0:05
FILTERING, DOWNFLOW, POST FILL
X X X X 0:30 X
*Cycles are non-adjustable, not shown in cycle sequence programming, and are in seconds.
ECOMIX has the same cycle sequence as SOFTENING.