52
Air Compressor - New
Verify and document the location of the air compressor: __________________________
Verify and document the manufacturer of the air compressor: __________________________
Verify and document the model number of the air compressor: __________________________
Verify and document the serial number of the air compressor: __________________________
Verify and document the air compressor on/off pressure settings: __________________________
Verify and document the air compressor power supply voltage: __________________________
Verify and document whether the air compressor(s) is/are installed correctly: Yes No
If No, explain: _________________________________________________________________________
Verify and document whether the air compressor(s) is/are wired correctly: Yes No
If No, explain: _________________________________________________________________________
Verify and document whether the air compressor(s) rotation is correct: Yes No
NOTE: If rotation incorrect on 3-phase motor, reverse any two of the three incoming
power wires to reverse the rotation
Verify and document if air compressor receiver tank auto-drain(s) is/are powered: Yes No
Verify and document the auto-drain(s) is configured for on time of ten (10) seconds and off time
frequency is twenty (20) minutes (maximum):
Yes No
Verify and document whether the auto-drain is/are plumbed to a drain: Yes No
Nitrogen Generator Equipment
Verify and document the location of the nitrogen generator(s): ________________________
Verify and document the quantity of the nitrogen generator(s): ________________________
Verify and document the model number of the nitrogen generator(s): ________________________
Verify and document the serial number of the nitrogen generator(s): ________________________
Verify and document whether the nitrogen generator(s) is/are installed correctly: Yes No
If No, explain: _________________________________________________________________________
Verify and document whether the nitrogen generator(s) is/are wired correctly: Yes No
If No, explain: _________________________________________________________________________
Programming of Nitrogen Generator’s Pressure Settings
Turn On/Off Power Switch to the On position
Verify and document the cut-in or turn-on pressure of the nitrogen generator is
3-5 psig (.2-.3 bar) below operating pressure of the fire sprinkler systems’ air
maintenance device(s): Yes No