EasyManua.ls Logo

Edwards DRYSTAR GV Series

Edwards DRYSTAR GV Series
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© Edwards Limited 2009. All rights reserved. Page 23
Edwards and the Edwards logo are trademarks of Edwards Limited.
INSTALLATION
A705-74-880 Issue K
1. Refer to Figure 7. Remove the red blanking caps from the cooling-water outlet port (3) and the cooling-water
inlet (as shown in Figure 1). Fill pump case with cooling-water and fit the outlet connection into the outlet port
(3) using sealant (Loctite 577 or equivalent).
2. Fit the end of your cooling-water supply pipeline to the Temperature Control Valve (TCV) with a suitable ½" BSP
adaptor using sealant (Loctite 577 or equivalent).
3. Fit the end of your cooling-water return pipeline to the outlet connection using a suitable ½" BSP adaptor using
sealant (Loctite 577 or equivalent).
4. Cooling-water supply lines should be rated to 7 bar working pressure and to 338°F (170°C).
Figure 7 - Cooling Schematic
3.10 Connect the shaft-seals purge and gas-ballast gas supplies
3.10.1 Introduction
Select the correct shaft-seals purge and gas-ballast requirements for your application. It is recommended that
nitrogen supply be connected to the gas systems if toxic, corrosive or flammable materials are to be pumped.
If a compressed air supply is required to the shaft-seal purge inlet, use the procedure in Section 3.10.2. The gas-
ballast system can deliver filtered atmospheric air to the pump gas-ballast inlet, therefore it may not be necessary
to connect an air supply to the gas-ballast system.
If required to connect nitrogen supplies to the shaft-seals inlet and to the gas-ballast system. Use the procedures in
Section 3.10.2 and Section 3.10.3.
1. TCV/Coolant inlet connection 2. Coolant outlet connection

Table of Contents

Related product manuals