EasyManua.ls Logo

Edwards DRYSTAR GV Series

Edwards DRYSTAR GV Series
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A705-74-880 Issue K
Page 24 © Edwards Limited 2009. All rights reserved.
Edwards and the Edwards logo are trademarks of Edwards Limited.
INSTALLATION
3.10.2 Connect the shaft-seals purge air or nitrogen supply
CAUTION
Your compressed air or nitrogen supply pressure must comply with the requirements of Section 2.2. If it does
not, the shaft-seals purge pipeline may become over-pressurised and the shaft-seals may fail.
Ensure that the compressed air or nitrogen gas supply must be clean and dry.
We recommend the installation of suitable non-relieving regulator pressure control devices, a pressure gauge, and
an automatically operated isolation-valve in your compressed air or nitrogen supply so that:
The shaft-seals purge air or nitrogen supply is on whenever the pump is on.
If you connect a nitrogen supply, the nitrogen supply is off whenever the pump is off.
Whenever the shaft-seals purge air or nitrogen supply is on, you must maintain the pressure to the shaft-
seals as specified in Section 2.2.
Use the following procedure to connect your shaft-seals purge air or nitrogen supply; A rigid metal (such as stainless
steel) pipeline with an outside diameter of ¼" (6.4mm) must be fitted for the air or nitrogen supply pipeline.
1. Refer to Figure 1. Remove the red blanking cap from the shaft-seals purge inlet (31).
2. Remove the ¼" (6.4mm ) compression nut and ferrule from the fittings kit and fit them finger-tight onto the
shaft-seals purge inlet connection (31).
3. Fit the end of the air or nitrogen supply pipeline to the shaft-seals purge inlet connection (31), then tighten the
nut to secure the pipeline in place.
3.10.3 Connect a nitrogen gas-ballast supply (optional)
To enable connection to the flow valve the nitrogen supply pipeline must terminate in a KF16 fitting.
If required a non venting (to atmosphere) nitrogen gas-ballast supply to the pump can be connected. The supply
should be set to shaft seal purge pressure. A non-venting (to atmosphere) nitrogen gas-ballast supply to the pump
must be connected if you pump dangerous gases.
When connecting a nitrogen supply to the gas-ballast system, it is recommend that you incorporate a suitable non-
relieving pressure gauge in the nitrogen supply pipeline.
Refer to Figure 8. Use the following procedure to connect a nitrogen supply to the gas-ballast system:
1. Undo and remove the clamp (9) and the NW16 trapped O-ring (10) and remove the air filter (11).
2. Use the clamp (9) and trapped O-ring (10) to connect your nitrogen supply pipeline to the gas-ballast flow valve
(8).
WARNING
If Hazardous gases are to be pumped, fit a suitable non-venting (to atmosphere) nitrogen supply to
the shaft-seals purge inlet, to prevent the escape of dangerous gases from the pump.
WARNING
If hazardous gases are to be pumped, fit a suitable non-venting (to atmosphere) nitrogen supply to
the gas-ballast system, to prevent the escape of dangerous gases from the pump.

Table of Contents

Related product manuals