Chapter 2: Installation and configuration
LaserSense 100 Aspirating Smoke Detector Installers Handbook 13
Below or above the ceiling installations
The detector is supplied with a docking station (as shown in Figure 4 on page
10). This allows the detector to sample from areas which may be at different air
pressure from the detector location. Typical uses are for air duct sampling and
allowing the installation of the detector in under-floor or ceiling voids or when
sampling from pieces of computer related equipment. See Figure 6 and Figure 7.
Figure 6: Installation of pipework above ceiling with exposed detector (piped exhaust)
Sampling pipe
Sampling hole
(4) Exhaust pipe
(5) False ceiling