Chapter 2: Installation and configuration
28 LaserSense 100 Aspirating Smoke Detector Installers Handbook
List of programmable functions
See your Remote or SenseNET documentation for more information on
programmable functions.
The following programmable functions are available:
• Device Type (reference only)
• Firmware Version
• Run-time Hours
• Watchdog Count (reference only)
• Device Text
• Reference Detector
• Reference Enable
• Reference Level
• Reference Back-off
• Flow Rate (reference only)
• Flow High Limit
• Flow Low Limit
• Flow Fault Delay
• Access Code
• Chart Recording Rate
• Separator Condition (reference
only)
• Separator Change Date
• Factory Default
Programmed isolate (discontinued)
This function is no longer supported. To isolate the detector, use the Isolate
function.
WARNING
To avoid potential safety risks, do not use the Programmed Isolate function.
If a detector is isolated (disabled) using Programmed Isolate, there is no visual
indication on the detector, command module, or control panel that the device is
not operational, and the function is not disabled automatically after 7 days.
The use of the Programmed Isolate function is entirely at the operator’s own risk.