UPS MTD 1000 / 1500 / 2000 / 3000
UPS MTD 1500L / 2000L
Technical Data
MTD Series
57
12. Technical Data
12.1 Device Specifications for Tower Housing
MTD model
1000
1500
1500L
2000
2000L
Power
Power in VA
1000
1500
2000
Power in W
625
938
1250
Bridging
period
Nominal load
6 min
-
4 min
-
Input
Nominal voltage
230 V AC
Input voltage area
170~ 300 VAC
Input frequency area
45~ 70 Hz Auto-sensing
Boost start threshold /
shut down
195.5 VAC ± 2 % / 205.5 V AC ± 2 %
Boost start threshold /
shut down
264.5 VAC ± 2 % / 254.5 V AC ± 2 %
Under-voltage warning
threshold/ All clear
170 VAC ± 2 % / 180 V AC ± 2 %
Over-voltage warning
threshold / All clear
300 VAC ± 2 % / 290 VAC ± 2 %
Output
Output voltage
Can be set on the LCD display to 220, 230, 240 V AC
Voltage tolerance
Line mode ± 15 %, Battery mode < 3 % RMS
Frequency tolerance
Line mode 50 Hz or 60 Hz, Battery mode ± 0.1 Hz
Power factor
0.625
Voltage form
Sinusoidal
Efficiency
> 80 %
DC start
Cold start
Yes
Switching
time
Typical
< 4 msec.
Battery
Nominal voltage
24 VDC
36 VDC
Number of blocks x
Nominal capacity / Block
2 x 7 Ah
3 x 7 Ah
-
3 x 7 Ah
-
Type
Closed, maintenance-free VRLA batteries
Life expectancy
approx. 5 years (depending on the environmental
conditions) option for 10 years
Charging time
approx. 5 hours
to 90 %
-
approx.
5 hours
to 90 %
-

Related product manuals