EasyManua.ls Logo

EFOY Pro 2400 - Page 50

Default Icon
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
Page 49
Permitted value ranges for Lead-acid, -gel & AGM batteries (12 V)
Factory
defaults
Min.
Max.
User-defined
value:
Switch-on voltage
12,3 V
11,0 V
13,0 V
Switch-off voltage
14,2 V
13,5 V
14,7 V
Switch-off voltage
(Hybrid)
14,7 V
13,5 V
15,5 V
Switch-off current
EFOY Pro 800
EFOY Pro 2400
2,0 A
4,0 A
1,0 A
4,0 A
10,0 A
10,0 A
Switch-on delay
60 s
2 s
300 s
Absorption time
180 min
0 min
300 min
Max. charge time
24 h
2 h
120 h
Altitude up to
1500 m
0 m
2000 m
Permitted value ranges for Lead-acid, -gel & AGM batteries (24 V)
Factory
defaults
Min.
Max.
User-defined
value:
Switch-on voltage
24.6 V
22.0 V
26.0 V
Switch-off voltage
28.4 V
27.0 V
29.4 V
Switch-off voltage
(Hybrid)
29,4 V
27,0 V
31,0 V
Switch-off current
EFOY Pro 800
EFOY Pro 2400
1.0 A
2.0 A
1.0 A
2.0 A
5.0 A
5.0 A
Switch-on delay
60 s
2 s
300 s
Absorption time
180 min
0 min
300 min
Max. charge time
24 h
2 h
120 h
Altitude up to
1500 m
0 m
2000 m

Table of Contents

Other manuals for EFOY Pro 2400

Related product manuals