Installation
Connections
Collective ue gas outlet under-pressure
Diameter and venting lengths of the
uegasoutlet/airsupply:
- Open system, with under-pressure
(calculated with thermal draft)
under atmospheric circumstances.
NOTE!
1. IPX0D at ue category B
23
and B
33
Diameter and venting lengths of the
uegasoutlet/airsupply:
- Closed system, with under-pressure
(calculated with thermal draft)
under atmospheric circumstances.
d
d
h
d
d
h
=d
=d
d
d
Dimensions cascade ue THISION L PLUS
Open system, underpressure
Output (80/60) d = minimum diameter Ø in mm
[kW] h = 2 - 5 h = 5 - 9 h = 9 - 13 h = 13 - 17
114 - 240 210 200 190 190
240 - 360 300 270 260 250
360 - 480 360 330 310 300
480 - 600 440 380 360 340
600 - 720 470 420 400 380
720 - 840 550 470 430 410
840 - 960 600 510 470 440
Dimensions cascade ue THISION L PLUS
Closed system, underpressure, parallel
Output (80/60) d = minimum diameter Ø in mm
[kW] h = 2 - 5 h = 5 - 9 h = 9 - 13 h = 13 - 17
114 - 240 240 220 220 220
240 - 360 330 300 290 270
360 - 480 390 370 350 330
480 - 600 460 410 390 380
600 - 720 500 460 440 420
720 - 840 550 500 470 460
840 - 960 600 540 510 490