60
Operation
Parameter listing
Menu
Submenu
Parameter
Name Description Range
Factory
settings
4. 2. 2 Slope LT: From 0.2 - 1.0
HT: From 1.0 - 3.5
0.6LT
1.3HT
Increase setting:
Increasestheow
temperature, especially at low
outside temperatures.
Reduce setting:
Reducestheowtemperature,
especially at low outside
temperatures.
flow temperature
low temperature level high temperature level
outdoor temperature
room temperature
setpoint
°C
°C
23
23
21
21
19
19
30
20
10
0
40
50
60
70
80
90
°C
510152025
3.5
3.0
2.5
2.0
1.8
1.5
1.3
0.8
1.0
0.6
0.4
0 -5 -10 -15 -20 -25 °C
0.8
0.6
1.0
0.4
0.2
4. 2. 3 O󰀨set O󰀨setheatinglineadjustableper°C LT: From -7°C to +7°C
HT: From -14°C to +14°C
0
0
4. 2. 4
Roominuenceproportional Only visible on the boiler if a room sensor
is connected
LT=2
HT=4
4. 2. 5 Max T Zone 1 Maximum Flow Temperature LT: From 20°C to 45°C
HT: From 20°C to 85°C
45°C
85°C
4. 2. 6 Min T Zone 1 minimum Flow Temperature LT: From 20°C to 45°C
HT: From 20°C to 85°C
25°C
20°C
4. 2. 7 Thermo regulation logic 0 = OFF, 1 = ON 0 - 1 0
4. 2. 8 Quick night setback 0 = OFF, 1 = ON 0 - 1 0
4. 2. 9 Heat request mode 0 = Standard
1 = RT Time Programs Exclusion
2 = Forcing Heat Demand
0 - 2 0
4. 3 Zone1 Diagnostics
4. 3. 4 Heat Request Z1 0 = OFF, 1 = ON
4. 3. 9 Heating rate 0 = OFF, 1 = ON
5 Zone2 Parameters (see Zone1, chapter 4)
6 Zone3 Parameters (see Zone1, chapter 4)