61
Operation
Parameter listing
Menu
Submenu
Parameter
Name Description Range
Factory
settings
24 Commercial Boiler
24. 0 General
24. 0. 2 Maximum Water temp 20 - 95 °C 95
24. 0. 3 Max CH Adjustable 0 - 100 % 100
24. 0. 4 Fan inc percentage 4 - 400 % 4
24. 0. 5 Altitude 0 - 3000 m 0
Boiler tank solar integration
0 = Absent
1 = Present
0 - 1 0
24. 0. 7 Emergency setpooint 20 - 90 °C 45
24. 3. Water Circulation
24. 3. 0 Max PWM Pump 61 - 95 % 95
24. 3. 1 Min PWM Pump 20 - 95 % 46
24. 3. 2 CH pump overrun 0 - 10 min. 5
24. 5 Domestic Hot Water
24. 5. 0 DHW Setpoint Temperature 40 - 65 °C 65
24. 5. 1 Comfort Function
0 = Disabled
1 = Time Based
2 = Always Active
0 = 2 0
24. 5. 2 System DHW Mode
0 = CH Only
1 = Storage with NTC
2 = Storage with Thermostat
0 - 2 0
24. 5. 3 Boiler DHW Mode
0 = CH Only
1 = Storage with NTC
2 = Storage with Thermostat
0 - 2 0
24. 5. 4 Anti-legionella Function 0 = OFF, 1 = ON 0
0 = OFF
1 = ON
24. 5. 5 Boiler DHW charge mode 0 - 2 0
0 = Charge
1 = Full charge
2 = Full charge Legio
24. 5. 6 System DHW charge mode 0 - 2 0
0 = Charge
1 = Full charge
2 = Full charge Legio
24. 5. 7 Boiler DHW Circulating Pump Release 0 - 2 0
0 = Release
1 = Time Program
2 = Special Time Program