Commissioning
AdjustmentofGasFittings
A
djustmentvaluesfornaturalgas
NaturalgasL/H TRIGONL
65-120
Gasconnection
pressure
mbar 20
CO
2
ma
x. %
8,80,2
CO
2
mi
n. %
8,20,2
MinimumandmaximumCO
2
v
alues
mustalwayshaveadifferenceof
0.3%.
A
djustmentofcombustionquality

Con
nectequipmentintermsofwater,
gas,andelectricity
Duetothedifferentignitionfeaturesof
naturalgasLLandnaturalgasE,an
adjustmentofthegas/airmixtureis
required.

Afte
rignition,thespecifiedCO
2
v
alue
atfullloadcanbeadjustedbyturning
theadjustmentscrew(2)

AdjustmentoftheCO
2
valueatsmall
loadbyturningtheadjustmentscrew
(1)atthegasfitting.
18
1
1
2
Ref
ittingfromnaturalgastoliquid
gas
Forarefittingtoanoperationusing
liquidgas,thefollowingfaceplates
mustbeused(availableasaset):
TRIGONL65:6,0mm
TRIGONL85:6,0mm
TRIGONL100:6,2mm
TRIGONL120:8,0mm
Adjustmentvaluesforliquidgas
Liquidgas TRIGONL
65-120
Gasconnection
pressure
mbar 50
CO
2
ma
x. %
9,80,2
CO
2
min. %
9,00,2
MinimumandmaximumCO
2
values
mustalwayshaveadifferenceof
0.3%.
2
e
n