PAR. DESCRIPTION M.U. RANGE EZ-HT EZ-MT EZ-LT
tdO Delay in door open alarm activation. min 0 ... 250 0 0 0
tAO Time delay for temperature alarm indication. min 0 ... 250 0 0 0
dAt
Alarm signalling end of defrost due to timeout.
n(0) = Alarm not activated; y(1) = Alarm activated.
flag n/y n n
rLO
Regulators locked by external alarm.
n(0) = Does not lock the regulators; y(1) = Locks the regulators.
flag n/y n n n
dOd
Enable utility switch-off on activation of door switch:
0 = Disabled; 1 = Disables fans;
2 = Disables the compressor; 3 = Disables fans and compressor.
num 0 ... 3 1 1 1
dAd Digital input activation delay. min 0 ... 255 0 0 0
OSP
Temperature value to be added to the Setpoint if reduced set enabled
(Economy function).
°C/°F -30.0 ... 30.0 0.5 0.5 0.5
LOC
Lock. Setpoint change shutdown. It is still possible to enter parameter
programming mode and modify them. n(0) = No; y(1) = Yes.
flag n/y n n n
PS1
PAssword 1.
When enabled (PS10), this password provides access to parameters.
num 0 ... 250 0 0 0
ndt
Display with decimal point
n(0) = No (integers only); y(1) = Yes (display with decimal point).
flag n/y y y y
CA1
Calibration 1. Positive or negative temperature value added to the
value read by Pb1.
°C/°F -12.0 ... 12.0 0.0 0.0 0.0
CA2
Calibration 2. Positive or negative temperature value added to the
value read by Pb2.
°C/°F -12.0 ... 12.0 0.0 0.0