- 5 -
E
N
Technical parameters
Supply
Supply terminals:
Supply voltage:
Consumption:
Supply voltage tolerance:
Backup battery type:
Measuring circuit
Measuring terminals:
Temperature range:
Hysteresis (sensitivity):
Diference:
Sensor:
Sensor failure indication:
Accuracy
Measuring accuracy:
Repeat accuracy:
Temperature dependance:
Number of function:
Output
Number of contacts:
Rated current:
Switching capacity:
Switching voltage:
Output indication:
Mechanical life:
Electrical life (AC1):
A1 - A2
AC230 V (AC50-60Hz), galvanically
isolated or AC/DC 24 V, not galvani-
cally isolated
max. 4 VA
-15 %; +10 %
CR 2032 (3V)
T1-T1 a T2-T2
-40.. +110 °C
adjustable within range 0.5...5 °C
adjustable 1 .. 50 °C
thermistor NTC 12 kΩ at 25 °C
displayed on LCD *
5 %
< 0.5 °C
< 0.1 % / °C
6
1x switching for each output (AgNi)
8 A / AC1
2000 VA / AC1, 240 W / DC
250 V AC1 / 30 V DC
symbol ON/OFF
1x10
7
1x10
5
up to 3 years
max. ±1s/ day at 23°C
1 min.
min. 10 years
100
daily , weakly, yearly
LCD display, with back light
-10.. +55 °C
-30.. +70 °C
4 kV (supply - output)
any
DIN rail EN 60715
IP 40
from front panel
/ IP 20 clips
III.
2
max.1x 2.5, max.2x1.5/ with sleeve
max. 1x2.5
90 x 35.6 x 64 mm
(230V) 127 g (24V) 120 g
EN 61812-1. EN 61010-1. EN 60730-2-9;
EN 60730-1; EN 60730-2-7
Time circuit
Real time back-up:
Accuracy:
Minimum interval:
Data stored for:
Program circuit
Number of memory places:
Program(SHT-3, SHT-3/2):
Data readout:
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage cathegory:
Pollution degree:
Max. cable size (mm
2
):
Dimensions:
Weight:
Standards:
* ERROR - sensor short circuit
NO SENSOR - interruption sensor