Service menu
2280073 Rev.1 Page 38
10.3.4 Set 12V Pb charging voltage
This is a sub-item of the "Set voltage" menu. It is used to set the charging voltage to 12V for
the operating mode for charging 12V lead-acid batteries.
Default setting: 14.8V Setting range: 9.0V to 16.0V
10.3.5 Set 12V LIO charging voltage
This is a sub-item of the "Set voltage" menu. It is used to set the charging voltage to 12V for
the operating mode for charging 12V lithium-ion batteries.
Default setting: 14.0V Setting range: 9.0V to 16.0V
10.3.6 Set 24V charging voltage
This is a sub-item of the "Set voltage" menu. It is used to set the charging voltage for the 24V
battery-charging mode.
Default setting: 28.8V Setting range: 27.0V to 30.0V
10.3.7 Set U-Shutdown
This is a sub-item of the "Set voltage" menu. It is used to set the output voltage for the
shutdown function. This function is only active in the operating mode "Charging LIO".
Default setting: 11.0V Setting range: 9.0V to 16.0V
10.3.8 Set U-Refresh
This is a sub-item of the "Set voltage" menu. It is used to set the output voltage for the refresh
function.
Default setting: 14.0V Setting range: 9.0V to 16.0V
10.3.9 Set 12V EPS voltage
This is a sub-item of the "Set voltage" menu. It is used to set the output charge voltage for the
operating mode 12V external power supply.
Default setting: 14.2V Setting range: 9.0V to 16.0V
10.3.10 Set 24V EPS voltage
This is a sub-item of the "Set voltage" menu. It is used to set the output charge voltage for the
operating mode 24V external power supply.
Default setting: 28.0V Setting range: 27.0V to 30.0V