Service menu
2280073 Rev.1 Page 39
10.4 Set voltage limits
The "Set voltage limit" menu is used to set the monitoring limits for overvoltage and
undervoltage.
10.4.1 Set Ua max. 12V
This is a sub-item of the "Set voltage limit" menu. It is used to set the monitoring limit for
overvoltage where output voltage is 12 V.
Default setting: 16.0V Setting range: 9.0V to 16.0V
10.4.2 Set Ua min. 12V
This is a sub-item of the "Set voltage limit" menu. It is used to set the monitoring limit for
undervoltage where output voltage is 12V.
Default setting: 7.0V Setting range: 7.0V to 10.0V
10.4.3 Set Ua max. 24V
This is a sub-item of the "Set voltage limit" menu. It is used to set the monitoring limit for
overvoltage where output voltage is 24V.
Default setting: 32.0V Setting range: 30.0V to 32.0V
10.4.4 Set Ua min. 24V
This is a sub-item of the "Set voltage limit" menu. It is used to set the monitoring limit for
undervoltage where output voltage is 24V.
Default setting: 14.0V Setting range: 14.0V to 20.0V