EasyManua.ls Logo

Eltek MultiCharger 1500 - Factory (default) settings

Eltek MultiCharger 1500
47 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Factory (default) settings
2280073 Rev.1 Page 44
Factory (default) settings
Selecting the "Factory settings" menu and pressing the "Enter" key restores the following
parameters to their default settings.
12V Pb charging voltage : 14.8V
12V LIO charging voltage : 14.0V
24V charging voltage : 28.8V
12V Pb trickle charge voltage : 13.4V
12V LIO trickle charge voltage : 13.4V
24V trickle charge voltage : 26.8V
Shutdown voltage : 11.0V
Refresh voltage : 14.0V
12V EPS voltage : 14.2V
24V EPS voltage : 28.0V
12V charging current limit : 80.0A/100.0A
24V charging current limit : 40.0A/50.0A
12V EPS current limit : 80.0A
24V EPS current limit : 40.0A
12V Ua max. : 16.0V
24V Ua max. : 32.0V
12V Ua min. : 7.0V
24V Ua min. : 14.0V
Switch back delay : 005min
Maximum charging time : 12h
Current limit 2 : 3.0A
Operating mode : battery charging mode 12V Pb
Autostart : enabled
24V operating modes : off
The MC1500 provides the option to make permanent changes to the default settings through
external software. In this case, the charger’s settings may vary from those shown above.
If the default settings are changed, this should be marked in the accompanying documentation.
Select language
The "Select language" menu can be used to select one of the following languages:
- German
- English
- French
- Dutch
- Italian
- Spanish
- Finnish
Each language is shown on the selection menu in that particular language.