Table 21 Power consumption and heat dissipation
VMAX 100K VMAX 200K VMAX 400K
Maximum power
and heat
dissipation at
<26°C and
>35°C
a
Maximum
total power
consumption
<26°C /
>35°C
(kVA)
Maximum
heat
dissipation
<26°C /
>35°C
(Btu/Hr)
Maximum
total power
consumption
<26°C /
>35°C
(kVA)
Maximum
heat
dissipation
<26°C /
>35°C
(Btu/Hr)
Maximum
total power
consumption
<26°C /
>35°C
(kVA)
Maximum
heat
dissipation
<26°C /
>35°C
(Btu/Hr)
System bay 1
Single engine
8.27 / 10.8 28,201 /
36,828
8.37 / 10.9 28,542 /
37,169
8.57 / 11.1 29,224 /
37,851
System bay 2
Single engine
b
8.13 / 10.4 27,723 /
35,464
8.33 / 10.6 28,405 /
36,146
8.43 / 10.7 28,746 /
36,487
System bay 1
Dual engine
6.44 / 8.8 21,960 /
30,008
6.74 / 9.1 22,983 /
31,031
7.04 / 9.4 24,006 /
32,054
System bay 2
Dual engine
b
N/A 6.7 / 8.8 22,847 /
30,008
6.9 / 9 23,529 /
30,690
a.
Power values and heat dissipations shown at >35°C reflect the higher power levels associated with both the battery recharge
cycle, and the initiation of high ambient temperature adaptive cooling algorithms. Values at <26°C are reflective of more steady
state maximum values during normal operation.
b.
Power values for system bay 2 and all subsequent system bays where applicable.
Table 22 Physical specifications
Bay configurations
a
Height
b
(in/cm)
Width
c
(in/cm)
Depth
d
(in/cm)
Weight
(max lbs/kg)
System bay, single-engine 75/190 24/61 47/119 2065/937
System bay, dual-engine 75/190 24/61 47/119 1860/844
a.
Clearance for service/airflow is the front at 42 in (106.7 cm) front and the rear at 30 in (76.2 cm).
b.
An additional 18 in (45.7 cm) is recommended for ceiling/top clearance.
c.
Measurement includes .25 in. (0.6 cm) gap between bays.
d.
Includes front and rear doors.
VMAX3 with HYPERMAX OS