46
Appendix G - SETPOINT Temperature
Set values to enable (ON) or disable (OFF) the temperature realy output. The instrument will proceed to the ON/
OFF working mode.
Example: set ON at 30 °C and OFF at 25 ° C
The output will be active for values lower than 30 ° C and it will switch off for values greater than 30 ° C , then
it’ll reactivate for values lower than 25 ° C. The difference between these two values (30 ° C and 25 ° C) is called
hysteresis. In order to avoid that the relay is switched on and off repeatedly avoid setting hysteresis values below 2 ° C.