8 C6.1.6/0117-1017/E
2.8.5 P&I diagram for ZXLE units
IMPORTANT
Absence of insulation on the liquid line in ZXLE units! Air moisture
condensation and lack of performance! Moisture will condensate on the
liquid line and cause water droplets. The liquid line can pick up additional heat
from the ambient which will adversely affect the sub-cooling desirable for the
liquid refrigerant before it enters the expansion valve. Both the suction and
liquid interconnecting piping between the ZX unit and the evaporator should
be insulated to avoid condensation.
Figure 4: P&I diagram for ZXLE units
High efficient Copeland Scroll compressor
Condenser with 1 or 2 fans
Liquid receiver with service valve
Plate heat exchanger for enhanced vapour injection
(EVI)
Expansion device for enhanced vapour injection (EVI)
Filter drier / sight glass combination
Service valve, liquid line
Service valve, suction line
Adjustable low-pressure switch (not factory mounted)
Non-adjustable high-pressure switch
Suction pressure sensor, low pressure
Pressure sensor, high pressure
Discharge temperature sensor
Ambient temperature sensor
Vapour in temperature sensor
Vapour out temperature sensor
Table 6: Legend of the P&I diagram for ZXLE units