Prearranged terminals /
Wiring diagram
Low pressure switch, optional; can be
ordered factory-installed.
Solenoid valve liquid line (not available on
ZXDE units)
Room thermostat for pump-down or direct
control
Sensor for evaporator or room
Sensor for evaporator or room (NTC10kΩ)
Table 8: Prearranged additional connections
Figure 8: Prearranged additional connections
NOTE: Depending on the required functionalities additional components might be necessary.
Please contact your local Application Engineering representative.
NOTE: Check the current limitations given by the controller relays.
NOTE: The solenoid valve function is not available on ZXDE units.
Table 9: Digital output specifications
Temperature control by means of an external room thermostat (not available on ZXDE units)
The temperature of a cold room or cooling cabinet can be controlled by means of an external room
thermostat (Digital Input DI3, parameter R07).
The parameters that must be changed to control a cooling cabinet or a cold room with a room
thermostat are listed in Table 10 below.
With these settings the controller will switch the compressor according to the status of the connected
device (room thermostat):
▪ if the input is closed, turn the compressor on (On-Off-compressor)
▪ if the input is open, turn the compressor off (On-Off-compressor)