Quick Start
Commissioning
10 Digistart IS User Guide
www.controltechniques.com Issue: 4
2.2.2 Current ratings for continuous operation (not bypassed)
AC53a utilisation code
The AC53a Utilisation Code defines the current rating and standard operating conditions for a non-bypassed soft starter.
The soft starter’s current rating determines the maximum motor size it can be used with. The soft starter's rating depends on the
number of starts per hour, the length and current level of the start, and the percentage of the operating cycle that the soft starter will
be running (passing current).
The soft starter’s current rating is only valid when used within the conditions specified in the utilisation code. The soft starter may
have a higher or lower current rating in different operating conditions.
Figure 2-3 AC53a utilisation code
Start current (multiple of motor full load current)
Starter current rating (amperes)
Starter current rating: The full load current rating of the soft starter given the parameters detailed in the remaining sections of the
utilisation code.
Start current: The maximum available start current.
Start time: The maximum allowable start time.
On-load duty cycle: The maximum percentage of each operating cycle that the soft starter can operate.
Starts per hour: The maximum allowable number of starts per hour.
Table 2-5 Current ratings - in-line (3-wire) connection, non-bypassed operation
AC53a 3-10:50-6
40 ºC <1000 metres
AC53a 3.5-15:50-6
40 ºC <1000 metres
AC53a 4-20:50-6
40 ºC <1000 metres
AC53a 4.5-30:50-6
40 ºC <1000 metres
Table 2-6 Current ratings - inside delta (6-wire) connection, non-bypassed operation
AC53a 3-10:50-6
40 ºC <1000 metres
AC53a 3.5-15:50-6
40 ºC <1000 metres
AC53a 4-20:50-6
40 ºC <1000 metres
AC53a 4.5-30:50-6
40 ºC <1000 metres